Create a new device | To create a new device, go to [Tools] - → [I/O Devices] or click the I/O Device Name: Give a device name. This name will be used in the Tag tag configuration window of the database accompanied by the station name‘Station Name’. |
Select a device type
| After selecting the [Ok] button on the previous step, the‘Serial Communication Configuration’dialog box will be popped up as shown in the following picture. In this window, select ‘LSIS Master-K H-Series PLC Cnet’ as the ‘Device Type’ and configure the appropriate communication parameters. Ensure that those parameters are matched with the device’s configuration. See the Communication Configuration section for more information. |
Create a station | Move to the [Station] tab of the ‘Serial Communication Configuration’ dialog box. In this dialog box, all the connected PLC stations can be configured and registered to the Xpanel. Each field can be configured as follows: Station Name: Give a name to the PLC. This name will be used in the database window accompanied by the 'Device Name’. Station Type: Choose the 'Master-K 500/1000' (no other type can be selected). Network ID: This field has no meaning in this driver (ignored in runtime). Station No.: This number must be matched with the one of PLC. See the Communication Configuration section for more information about the remaining parameters. |
...
*If communication type is RS-485, configure baud rate by the loader.
Address Notation
Refer to the table below fir for available device ranges.
...
Symbol | Range | Size | Access |
P | P0 - P63F | 64 | R/W |
M | M0 - M203F | 192 | R/W |
L | L0 - L63F | 64 | R/W |
K | K0 - K31F | 32 | R/W |
F | F0 - F63F | 64 | R |
T | T0 - T256 | 256 | R/W |
C | C0 - C256 | 256 | R/W |
D | D0 -D9999 | 10000 | R/W |
S | S0 - S99 | 100 | R/W |
Communication Cable Wiring
RS-232C | |
RS-422 | The wiring in the terminal resistance must be 330 Ω. To improve the stability of communication, devices should connect through SG, using STP cables. Shielded cables must be earthed. |
RS-485 | The wiring in the terminal resistance must be 120 Ω. When using RS-485, connect SDA and SDB, but disconnect RDA and RDB. To improve the stability of communication, devices should connect through SG, using STP cables. Shielded cables must be earthed. |