Create a new device | To configure the communication device of LSIS PLC, go to [Tools] - → [I/O deviceDevices] or click the I/O Device Name: Give a device name. This name will be used in the Tag tag configuration window of the database accompanied by the Station Name‘Station Name’. |
Select a device type | After selecting [Ok] on the previous step, the ‘Ethernet Communication Configuration’ dialog box will pop up as shown in the following picture. Select ‘Fatek PLC Enet’ in the ‘Device Type’ dropdown menu, and choose appropriate communication parameters. Those parameters must be matched with the PLC. See the Communication Configuration section for more information. |
Create a station | Move to the [Station] tab of the ‘Ethernet Communication Configuration’ dialog box and click [Add Station]. In this dialog box, all the connected PLC stations can be configured and registered to the Xpanel. Station Name: Give a name to the PLC. This name will be used in the database window accompanied by the 'Device Name'. Station Type: Choose the 'FATEK PLC' (no other type can be selected). Network ID: This field has no meaning in this driver (ignored during runtime). IP Address: Input IP Address FATEK PLC Socket Port No.: Input Major Port FATEK PLC. 16Bit Data Swap: This field has no effect. 32Bit Data Swap: This field has no effect. String Data Swap: This field has no effect. Using Checksum: This field has no effect. Comm. Error Message Pop up: When this item is checked, Xpanel displays a communication error message box for every Rx and Tx error. Otherwise (unchecked), Xpanel does not display a message for communication errors. This message box will close automatically after a few seconds. See the Communication Configuration section for more information about the remaining parameters. |
Communication Setting: FATEK PLC
1. IP Setting
...
Go to the [General] tab to set the IP address, Subnet Mask, and Gateway.
Check the ‘Remote Config’ box to enable it.
Select ‘Server’ for the ‘Operation Mode’.
...
Go to the [Misc.] tab to set the Major Port, on the 'FATEK Service Port Number'.
After finishing the parameter setting, press the [OK] button.
Address Notation
...
Name | Symbol | Digital | Analog | |
16-Bit | 32-Bit | |||
Input discrete | X | X00-X9999 | WX00-WX9984 | DWX00-DWX9984 |
Output relay | Y | Y00-Y9999 | WY00-WY9984 | DWY00-DWY9984 |
Internal relay | M | M00-M9999 | WM00-WM9984 | DWM00-DWM9984 |
Step relay | S | S00-S9999 | WS00-WS9984 | DWS00-DWS9984 |
Timer discrete | T | T00-T9999 | WT00-WT9984 | DWT00-DWT9984 |
Counter discrete | C | C00-C9999 | WC00-WC9984 | DWC00-DWC9984 |
Timer register | TMR |
| RT00-RT9999 | DRT00-DRT9999 |
Counter register | CTR |
| RC00-RC9999 | DRC00-DRC9999 |
Data register | HR |
| R00-R65535 | DR00-DR65535 |
Data register | DR |
| D00-D65535 | DD00-DD65535 |
(1) Word tag is supported by 16-Bit only.
(2) Digital address is used only for digital tags.
(3) The 32-Bit address is used only for 32-Bit analog tags.
...
You can configure the cable and allocation pin number of RJ45 as shown below.
...
RJ45 Connector | RJ45 Jack |
Direct Cable: Host ↔︎ HUB
...
Cable | No | Color | Color | No | Cable |
1 | Orange/White | Orange/White | 1 | ||
2 | Orange | Orange | 2 | ||
3 | Green/White | Green/White | 3 | ||
4 | Blue | Blue | 4 | ||
5 | Blue/White | Blue/White | 5 | ||
6 | Green | Green | 6 | ||
7 | Brown/White | Brown/White | 7 | ||
8 | Brown | Brown | 8 |
Crossover Cable: Host ↔︎ Host
...
Cable | No | Color | Color | No | Cable |
1 | Orange/W | Green/W | 1 | ||
2 | Orange | Green | 2 | ||
3 | Green/W | Orange/W | 3 | ||
4 | Blue | Blue | 4 | ||
5 | Blue/W | Blue/W | 5 | ||
6 | Green | Orange | 6 | ||
7 | Brown/W | Brown/W | 7 | ||
8 | Brown | Brown | 8 |