The alarm summary object allows the user to monitor the desired alarms in a single object. The object displays detailed information about the alarm and displays up to 500 alarm messages.

Settings

Click Insert > Alarm Summary or click the icon (blue star) and click on the page to bring up the configuration window as shown below:

Image Removed

 

Item

Description

Active Alarms

Displays the currently triggered alarms.

Shelved Alarms

Displays the shelved alarms.

Historical Alarms

Documents every alarm status change.

Label Filter

Allows the user to decide which alarms they want to view based on labels.

Check All

Selects all alarm messages in a specific tab.

Active

Checking and unchecking this box will display or hide, respectively, the active alarms.

Cleared

Checking and unchecking this box will display or hide, respectively, the cleared alarms.

Active, Ack.

Checking and unchecking this box will display or hide, respectively, the acknowledged-active alarms.

Cleared, Ack.

Checking and unchecking this box will display or hide, respectively, the acknowledged-cleared alarms.

Acknowledge

Sets an active or cleared alarm to “Active, Ack” or “Clear, Ack”.

Shelve

Suppresses an alarm.

Unshelve

Removes the suppression of an alarm. This button is located in the Shelved Alarms tab.

Time Dropdown

Displays the alarm statuses for the amount of time chosen (i.e. 10 min would display the last 10 minutes of alarm statuses).

Delete

Removes an alarm status from the Alarm Summary.

Item

Description

Active Alarms

Displays the currently triggered alarms.

Shelved Alarms

Displays the shelved alarms.

Historical Alarms

Documents every alarm status change.

Label Filter

Allows the user to decide which alarms they want to view based on labels.

Check All

Selects all alarm messages in a specific tab.

Active

Checking and unchecking this box will display or hide, respectively, the active alarms.

Cleared

Checking and unchecking this box will display or hide, respectively, the cleared alarms.

Active, Ack.

Checking and unchecking this box will display or hide, respectively, the acknowledged-active alarms.

Cleared, Ack.

Checking and unchecking this box will display or hide, respectively, the acknowledged-cleared alarms.

Acknowledge

Sets an active or cleared alarm to “Active, Ack” or “Clear, Ack”.

Shelve

Suppresses an alarm.

Unshelve

Removes the suppression of an alarm. This button is located in the Shelved Alarms tab.

Time Dropdown

Displays the alarm statuses for the amount of time chosen (i.e. 10 min would display the last 10 minutes of alarm statuses).

Delete

Removes an alarm status from the Alarm Summary.

Property Editor

Anchor
Top
Top
Feature Description

The Alarm Summary object lets users track and manage alarms in one tool. It can display times, names, values, and current statuses. Alarms are filterable by using Group and Level labels. Shelving alarms can also help declutter the Alarm Summary object’s Active Alarm tab. Each Alarm Summary object has Basic Properties, Appearance, and Transform options. This allows users to customize the content, look, and characteristics. For in-depth descriptions of elements and design options, visit Alarm Summary Information.

Designer Functionalities

The Canvas Simulator can operate a project with an Alarm Summary object that displays up to 150 alarms reliably. Likewise, a physical Xpanel can reliably do the same with up to 1,000 alarms. The operating speeds of both the Simulator and a physical Xpanel will depreciate with the creation of more alarms. Click Insert > Alarm Summary,or the Insert Alarm Summary icon in the toolbar, and click and drag on the page to bring up the Alarm Summary object as shown to the right:

Image Added

Properties

Content

Controls which type of data is shown in the column.

Name

Assigns a name to the header of the column.

Width

Assigns the default horizontal distance for the column. This can be changed while in runtime.

Format

Selects the string style of the data type.

Precision

Selects the number of decimal places to follow a value.

Add Column

Allows the user additional columns for their Alarm Summary.

Provides ways to customize the user’s Alarm Summary.

Image Removed

Item

Description

(blue star)

Expands each section within the Property Editor pane.

(blue star)

Collapses each section within the Property Editor pane.

Name

Allows the user to decide which name they want for the Alarm Summary.

 

 

 

Appearance

Image Removed

Visible

Controls whether the Alarm Summary is displayed or hidden. A tag may be bound to this property to control the status in runtime.

Opacity

Controls the transparency of the Alarm Summary. A tag may be bound to this property to control the status in runtime.

Blinking

Controls whether the Alarm Summary blinks. A tag may be bound to this property to control the status in runtime.

Blink Interval(ms):

Controls how often the Alarm Summary blinks. A tag may be bound to this property to control the status in runtime.

Background Color

Controls the color of the cells within the Alarm Summary. A tag may be bound to this property to control the status in runtime.

Active Color

Controls the color in which active alarms are displayed. A tag may be bound to this property to control the status in runtime.

Active Acknowledged Color

Controls the color in which active acknowledged alarms are displayed. A tag may be bound to this property to control the status in runtime.

Cleared Color

Controls the color in which cleared alarms are displayed. A tag may be bound to this property to control the status in runtime.

Cleared Acknowledged Color

Controls the color in which cleared acknowledged alarms are displayed. A tag may be bound to this property to control the status in runtime.

Font Name

Controls the font style of the displayed alarm text.

 

 

Location

Image Removed

Z index

Controls the layering of objects. Objects with a lower Z-index will lay on top of objects with a higher Z-index. The lowest Z-index is 0.

X

Controls the horizontal placement of an object. A tag may be bound to this property to control the status in runtime.

Y

Controls the vertical placement of an object. A tag may be bound to this property to control the status in runtime.

Width

Controls the horizontal distance of an object. A tag may be bound to this property to control the status in runtime.

Height

Controls the vertical distance of an object. A tag may be bound to this property to control the status in runtime.

Rotation

Controls the rotational orientation of an object. A tag may be bound to this property to control the status in runtime.

 

 

 

 

Actions

Image Removed

Touch

Controls whether the object responds to touch or not. A tag may be bound to this property to control the status in runtime.

On Press - Delay (ms)

Assigns how long, in ms, after touching an object that action occurs.

On Press - Action

Assigns a specific function to occur when an object is touched.

On Release - Delay (ms)

Assigns how long, in ms, after releasing touch on an object that action occurs.

On Release - Action

Assigns a specific function to occur when an object is released from being touched.

On Double Click - Interval (ms)

Assigns how long, in ms, the interval between two clicks constitutes a double click.

On Double Click - Action

Assigns a specific function to occur when an object is double-clicked.

Permissions

Assigns accessibility parameters for touching the object.

 

Display Configuration

Image Removed

Display Header

Controls whether the header of each column is shown or not. A tag may be bound to this property to control the status in runtime.

Display Outlines

Controls whether the borders between cells are shown or not. A tag may be bound to this property to control the status in runtime.

Display User Controls

Controls whether control buttons are shown or not. A tag may be bound to this property to control the status in runtime.

 

Filters

Image Removed

Show Active Acknowledged

Feature TBD. A tag may be bound to this property to control the status in runtime.

Show Active Unacknowledged

Feature TBD. A tag may be bound to this property to control the status in runtime.

Show Cleared Acknowledged

Feature TBD. A tag may be bound to this property to control the status in runtime.

Show Cleared Unacknowledged

Feature TBD. A tag may be bound to this property to control the status in runtime.

Initial Tab

Controls the starting tab on the initialization of the project. Default is the “Active Alarms” tab.

 

 

 

 

 

 

Active Tab

Image Removed

Visible

Controls whether the “Active Alarms” tab is visible or not. A tag may be bound to this property to control the status in runtime.

Content

Controls which type of data is shown in the column.

Name

Assigns a name to the header of the column.

Width

Assigns the default horizontal distance for the column. This can be changed while in runtime.

Format

Selects the string style of the data type.

Precision

Selects the number of decimal places to follow a value.

Add Column

Allows the user additional columns for their Alarm Summary.

 

 

 

 

 

 

Shelved Tab

Image Removed

Visible

Controls whether the Shelved Alarms tab is visible or not. A tag may be bound to this property to control the status in runtime.

Content

Controls which type of data is shown in the column.

Name

Assigns a name to the header of the column.

Width

Assigns the default horizontal distance for the column. This can be changed while in runtime.

Format

Selects the string style of the data type.

Precision

Selects the number of decimal places to follow a value.

Add Column

Allows the user additional columns for their Alarm Summary.

 

 

 

 

 

 

Historical Tab

Image Removed

Visible

Controls whether the “Historical Alarms” tab is visible or not. A tag may be bound to this property to control the status in runtime.

To ensure the property windows are enabled, click View > Properties > Basic Properties, Appearance, Transform, or Actions and check the boxes.

Basic Properties

The Basic Properties window allows changing the displayed content and formatting within the object. The object’s name will show up in place of Basic Properties, as pictured to the right:

Image Added

The Appearance pane enables the use of colors and selections to alter visible characteristics.

Image Added

Transform

The Transform tab provides adjustable properties that reshape or move the object.

Image Added

Actions

There are currently no applicable actions for the Alarm Summary object. This is intended, and there are no plans to add this capability.

Image Added

Runtime Functionalities

Filtering

When running the program, the user can select the Label Filter option in the Alarm Summary to display the alarms with a specific label. One or multiple labels may be applied at once. All active, cleared, and acknowledged alarms with the selected labels will be displayed in the Active Alarm tab of the Alarm Summary. If an active alarm has more than one label, it will be displayed when any of its labels are selected. The same can be done in the historical tab with active, cleared, acknowledged, and shelved alarms.

Image Added

Acknowledging

The user can acknowledge alarms to confirm they have been seen and trigger Acknowledge actions. If a cleared alarm is acknowledged, it will move from Active Alarm to Historical Alarm. Otherwise, any alarm will stay on the page until deleted. Users can check or uncheck the boxes for Active, Cleared, Active, Ack., and Cleared, Ack to show or hide certain statuses.

Image Added

Shelving

The user can shelve alarms to temporarily hide them from the Active Alarm tab. Shelve acts like a snooze button for a specified time interval that the user sets. After the interval, the alarm will unshelve and reappear in the Active Alarm tab. The user can bypass the set timer by clicking the Unshelve button in the Shelved Alarm tab.

Image Added
Image Added

Historical

The Historical Alarm tab creates a new record whenever an alarm status changes. The user can check a past alarm along with the status it was changed to, the time it was changed, and the value it had when it was changed. The logged alarms are filterable and deletable for better organization.

Image Added