Create a new device

To create a new device, go to [Tools] - [I/O Devices] or click the (blue star) icon on the main toolbar.

I/O Device Name: Give a device name. This name will be used in the Tag tag configuration window of the database accompanied by the station name‘Station Name’.

Select a device type

 

After selecting the [Ok] button on the previous step, the‘Serial Communication Configuration’dialog box will be popped up as shown in the following picture.

In this window, select ‘LSIS Master-K H-Series PLC Cnet’ as the ‘Device Type’ and configure the appropriate communication parameters. Ensure that those parameters are matched with the device’s configuration. See the Communication Configuration section for more information.

Create a station

Move to the [Station] tab of the ‘Serial Communication Configuration’ dialog box. In this dialog box, all the connected PLC stations can be configured and registered to the Xpanel.

Each field can be configured as follows:

Station Name: Give a name to the PLC. This name will be used in the database window accompanied by the 'Device Name’.

Station Type: Choose the 'Master-K 500/1000' (no other type can be selected).

Network ID: This field has no meaning in this driver (ignored in runtime).

Station No.: This number must be matched with the one of PLC.

16Bit Data Swap: This field has no meaning in this driver.

32Bit Data Swap: This field has no meaning in this driver.

Using Checksum: This field has no meaning in this driver.

Comm. Error Message Pop Up: When this item is checked, Xpanel displays a communication error message box for every Rx and Tx error. Otherwise (unchecked), Xpanel does not display a message for communication errors. This message box will close automatically after a few secondsSee the Communication Configuration section for more information about the remaining parameters.

Master-K 500/1000 DIP SWITCH Configuration

...

*If communication type is RS-485, configure baud rate by the loader.

Address Notation

Refer to the table below fir for available device ranges.

...

Symbol

Range

Size

Access

P

P0 - P63F

64

R/W

M

M0 - M203F

192

R/W

L

L0 - L63F

64

R/W

K

K0 - K31F

32

R/W

F

F0 - F63F

64

R

T

T0 - T256

256

R/W

C

C0 - C256

256

R/W

D

D0 -D9999

10000

R/W

S

S0 - S99

100

R/W

Communication Cable Wiring

RS-232C

RS-422

The wiring in the terminal resistance must be 330 Ω. To improve the stability of communication, devices should connect through SG, using STP cables. Shielded cables must be earthed.

RS-485

The wiring in the terminal resistance must be 120 Ω. When using RS-485, connect SDA and SDB, but disconnect RDA and RDB. To improve the stability of communication, devices should connect through SG, using STP cables. Shielded cables must be earthed.