Create a new device
| To create a new device, select [Tools] → [I/O Devices] or click the I/O Device Name: Give a device name. This name will be used in the tag database, accompanied by the ‘Station Name’. |
Select a device type
| After selecting the [Ok] button in the previous step, the ‘Serial communication Configuration’ dialog box will appear as shown in the following picture: In this window, set the 'Device Type' to ‘SIEMENS S7 PPI Direct’ and configure the remaining communication parameters. These parameters must match those chosen for the PLC. The parameters should be set to the following values: Baud Rate: 9600 or 19200 (must be matched with the PLC) Parity: Even Data Bits: 8 Bits Stop Bits: 1 Bit RTS/CTS: OFF Comm. Type: RS485 See the Communication Configuration section for more information about the remaining parameters. |
Create a station | Move to the [Station] tab of the 'Serial Communication Configuration' dialog box. In this dialog box, connected PLC stations can be configured and registered to the Xpanel. Each field can be configured with the following rules: Station Name: Give a name to the PLC. This name will be used in the tag database, accompanied by the ‘Device Name’. Station Type: Choose ‘S7’ (this is the only available option). Network ID: N/A Station No: Specify a decimal number between 0 and 126. This number must match the station chosen for the PLC. See the Communication Configuration section for more information about the remaining parameters. |
...
Tag Type | Format | Example |
Analog | [Symbol][Address] | VW064 |
Digital | [Symbol][Address].[Bit Number] or [Symbol][Address][Bit Number] | M012.3 or M0123 |
Address: decimal number (0 – 65535)
Bit Number: decimal number (0 – 7)
...
Symbol | Description | Word Notation | Bit Notation | Type | Access |
I | Input | - | I7.7 | Digital | R |
Q | Output | - | Q7.7 | Digital | R/W |
M | Internal Memory | - | M31.7 | Digital | R/W |
SM | Special Memory | - | SM85.7 | Digital | R/W |
T | Timer | - | T127 | Digital | R |
C | Counter | - | C127 | Digital | R |
IW | Input | IW7 | - | Analog | R |
QW | Output | QW7 | - | Analog | R/W |
MW | Internal Memory | MW31 | - | Analog | R/W |
SMW | Special Memory | SMW85 | - | Analog | R/W |
VW | Variable Memory | VW4095 | - | Analog | R/W |
TW | Timer SV | TW127 | - | Analog | R |
CW | Counter SV | CW127 | - | Analog | R |
Communication Cable Wiring
...