Versions Compared

Key

  • This line was added.
  • This line was removed.
  • Formatting was changed.

...

Create a new device

 

To create a new device, select [Tools] → [I/O Devices] or click the (blue star) icon in the toolbar. The following picture shows the first step in creating a new device:

I/O Device Name: Give a device name. This name will be used in the tag database, accompanied by the ‘Station Name’.

Select a device type

 

After selecting the [Ok] button in the previous step, the ‘Serial communication Configuration’ dialog box will appear as shown in the following picture:

In this window, set the 'Device Type' to ‘SIEMENS S7 PPI Direct’ and configure the remaining communication parameters. These parameters must match those chosen for the PLC.

The parameters should be set to the following values:

Baud Rate: 9600 or 19200 (must be matched with the PLC)

Parity: Even

Data Bits: 8 Bits

Stop Bits: 1 Bit

RTS/CTS: OFF

Comm. Type: RS485

See the Communication Configuration section for more information about the remaining parameters.

Create a station

Move to the [Station] tab of the 'Serial Communication Configuration' dialog box. In this dialog box, connected PLC stations can be configured and registered to the Xpanel.

Each field can be configured with the following rules:

Station Name: Give a name to the PLC. This name will be used in the tag database, accompanied by the ‘Device Name’.

Station Type: Choose ‘S7’ (this is the only available option).

Network ID: N/A

Station No: Specify a decimal number between 0 and 126. This number must match the station chosen for the PLC.

See the Communication Configuration section for more information about the remaining parameters.

...

Tag Type

Format

Example

Analog

[Symbol][Address]

VW064

Digital

[Symbol][Address].[Bit Number] or

[Symbol][Address][Bit Number]

M012.3 or M0123

  • Address: decimal number (0 – 65535)

  • Bit Number: decimal number (0 – 7)

...

Symbol

Description

Word Notation

Bit Notation

Type

Access

I

Input

-

I7.7

Digital

R

Q

Output

-

Q7.7

Digital

R/W

M

Internal Memory

-

M31.7

Digital

R/W

SM

Special Memory

-

SM85.7

Digital

R/W

T

Timer

-

T127

Digital

R

C

Counter

-

C127

Digital

R

IW

Input

IW7

-

Analog

R

QW

Output

QW7

-

Analog

R/W

MW

Internal Memory

MW31

-

Analog

R/W

SMW

Special Memory

SMW85

-

Analog

R/W

VW

Variable Memory

VW4095

-

Analog

R/W

TW

Timer SV

TW127

-

Analog

R

CW

Counter SV

CW127

-

Analog

R

Communication Cable Wiring

...