First, check if the protective film is removed. The protective film is only there for temporary protection of the product. It must be removed before operating the product. If there seems to be a problem even when the protective film is removed, please refer to the following steps.

...

The way can be only used when the preset below is applied.

Xpanel Calibration

...

Using Long-

...

Touch

a) Select the [Configure] button in the [Ethernet Loader] ‘Ethernet Loader’ dialog box.

...

b) Check the box Hold ‘Hold time(sec) for Touch CalibrationCalibration’ and set touch time in the range of 30 seconds to 32767 seconds. Select the [Save and Quit] button.

...

c) When the location is not recognized, press and hold a random point on the Xpanel screen (the default value is 30 seconds).

...

d) Click the center of the crosshair according to the introduction.

...

e) A confirmation notification of calibration completion will popup.

...

  • Setting in the [Xpanel Config] ‘Xpanel Config’ dialog box

When the problem occurs in an emergency situation and you cannot initiate calibration by the press and hold method, you may connect a mouse to the USB host of Xpanel and perform calibration easily.

Xpanel Calibration

...

Using Mouse

a) You can connect a mouse to the USB host port of the Xpanel. Click the screen as shown by the below numbered sequence to bring up the [Xpanel Config] dialog box.

...

b)Select [Touch Calibration].

...

c) Click the center of crosshair according to the introduction.

...

d) A confirmation notification of calibration completion will popup.

...

(2) There is no response after the screen is touched.

...