Communication Setup: Xpanel

Select [Tools] - [I/O Devices] or click the (blue star) icon from the main toolbar.

...

I/O Device Type: Select ‘Ethernet Device’. The Device Name device name will be used in the Station Name and Tag Configuration ‘Station Name’ and tag configuration of the database.

Select [Ok] for the ‘Ethernet Communication Configuration’ dialog box to appear.

...

Station Name

Give a name to the PLC. This name will be used in the database window accompanied by the ‘Device Name’.

Station Type

Choose the ‘MicroLogix’ (no other type).

Network ID

This field has no effect.

Socket Port No.

The default is set as 4481 for MicroLogix.

16Bit Data Swap

Data is obtained by swapping bytes of the word- or double-word-sized data.

32Bit Data Swap

Data is obtained by swapping words in double-word-sized data.

String Data Swap

Data is obtained by switching bytes of string word data.

Comm. Error Message Pop Up

With this feature ON, the communication error message appears when Xpanel detects a “Send/Receive” error.

Fast Mode

This field has no effect.

Fixed ATVXEL XPANEL Socket Port

Enables the ATVXEL XPANEL Socket Port No.

ATVXEL XPANEL Socket Port No.

Choose a Socket Port No. for the Xpanel.

I/O Device Write Enable

Enables writing to the I/O device.

Data Request Size Limit

Enables the 'WORD' and ‘BIT’ boxes below. Input the maximum word and bit data desired.

See the Communication Configuration section for more information.

Communication Configuration

1. Ethernet IP Setup

  • Run RSLogix 500.

  • Select [Comms] → [Upload…] from the menu, and upload a project.

...

  • Configure and save the IP Address, Subnet Mask, and Gateway Address.

  • Select [Comms] → [Download..], and download the setting to PLC.

Address and Function Codes

Address Format

Image Removed

Tag Type

Format

Image Removed

Supported Symbols

Example

Analog

[Symbol][Decimal Code]

X201 or Y300

Digital

[Symbol][Decimal Code]

E0201 or M9900

Supported Symbols

Symbol

Bit Range

Word Range

Name

O

O:0.0/0 – O:30.255/15

O:0.0 – O:30.255

Output

I

I:0.0/0 – I:30.255/15

I:0.0 – I:30.255

Input

S

S:0/0 – S:163/15

S:0 – S:163

Status

B

B3:0/0 – B3:255/15

B9:0/0 – B255:255/15

B3:0/0 – B3:255/15

B9:0/0 – B255:255/15

Binary

N

N7:0/0 – N7:255/15

N9:0/0 – N255:255/15

N7:0 – N7:255

N9:0 – N255:255

Integer

F

F8:0 – F255:255

  • Registration is allowed in Float only.

Float

L

L9:0 – L255:255

  • Registration is allowed in UINT32, INT32 only.

Long

ST

ST9:0 – ST255:255

String

T

T4:0.0/0 – T4:255.2/15

T9:0.0/0 – T255:255.2/15

 

Txx:nn.0/15 = Enable(EN)

Txx:nn.0/14 = Timer Timing(TT)

Txx:nn.0/13 = Done(DN)

T4:0.0 – T4:255.2

T9:0.0 – T255:255.2

 

Txx:nn.1 = Preset Value(PRE)

Txx:nn.2 = Accumulated Value(ACC)

Timer

C

C5:0.0/0 – C5:255.2/15

C9:0.0/0 – C255:255.2/15

 

Cxx:nn.0/15 = Count up enable(CU)

Cxx:nn.0/14 = Count down enable(CD)

Cxx:nn.0/13 = Done(DN)

Cxx:nn.0/12 = Overflow(OV)

Cxx:nn.0/11 = Underflowt(UN)

Cxx:nn.0/10 = Update Accumulator(UA)

C5:0.0 – C5:255.2

C9:0.0 – C255:255.2

 

Cxx:nn.1 = Preset (PRE)

Cxx:nn.2 = Accumulated Value(ACC)

Counter

R

R6:0.0/0 – C6:255.2/15

R9:0.0/0 – R255:255.2/15

 

Rxx:nn.0/15 = Enable(EN)

Rxx:nn.0/14 =Update Enable(EU)

Rxx:nn.0/13 = Done(DN)

Rxx:nn.0/12 = Stack Empty(EM)

Rxx:nn.0/11 = Error(ER)

Rxx:nn.0/10 = Upload(UL)

Rxx:nn.0/9 = Inhibit(IN)

Rxx:nn.0/8 = Found(FD)

R6:0.0 – R6:255.2

R9:0.0 – R255:255.2

 

Rxx:nn.1 = Length value

Rxx:nn.2 = position value

Control

Communication Cable Wiring

This is an interface for communication between the TOUCH/PPC and the Device by Ethernet. This complies with IEEE802.3 for 10Base/100BaseTX. Refer to the PIN number and cable for RJ45 as shown below.

...

RJ45 Connector

RJ45 Jack

Image AddedImage Added

Direct Cable: Host <-> HUB

...

↔︎ HUB

Cable

No

Color

Color

No

Cable

Image Added

1

Orange/White

Orange/White

1

Image Added

2

Orange

Orange

2

3

Green/White

Green/White

3

4

Blue

Blue

4

5

Blue/White

Blue/White

5

6

Green

Green

6

7

Brown/White

Brown/White

7

8

Brown

Brown

8

Crossover Cable: Host <-> ↔︎ Host

...

Cable

No

Color

Color

No

Cable

Image Added

1

Orange/White

Green/White

1

Image Added

2

Orange

Green

2

3

Green/White

Orange/White

3

4

Blue

Blue

4

5

Blue/White

Blue/White

5

6

Green

Orange

6

7

Brown/White

Brown/White

7

8

Brown

Brown

8