Create a new device | To configure the communication device of LSIS PLC, select [Tools] → [I/O Devices] or click the I/O Device Name: Type the device name to identify the equipment. This name will be used in the Tag tag configuration window of the database accompanied by the ‘Station Name’. |
Select a device type | After selecting [Ok] in the previous step, the ‘Serial Communication Configuration’ dialog box will pop up. Select ‘LSIS GLOFA PLC Cnet’ as the ‘Device Type’, and configure the parameters accordingly. Comm. Port: COM1 Select 'COM1'. When the RS-232 communication type of COM1 port is used, a 9P DSUB connector is used. When RS-422/485 communication type of COM1 port is used, the 5P plug connector is used. Baud rate: 9,600 The configuration of the communication speed of Xpanel must be the same as the LSIS GLOFA PLC. If the speed of both devices is different, they will not communicate with each other. Parity: None Data bits: 8 bits Stop bits: 1 bit RTS/CTS: OFF RTS/CTS control is used for half-duplex communication. This example does not use RTS/CTS control. Retry No.: 3 If communication failed with the devices, it will try to reconnect 3 times. Time Out: 30 The time out count will be 30 seconds. Using Dial Up Modem: Not Select This item can be chosen only when using the Dial Up modem. See the Communication Configuration section for more information about the remaining parameters. |
Create a station | Move to the [Station] tab of the ‘Serial Communication Configuration’ dialog box and click the [Add Station] button. The ‘Station’ dialog box will pop up. Configure the contents and click the [OK] button. Station Name: ST When the device number exceeds two, the station number is used to differentiate between the devices on the Xpanel. Station Type: Select ‘DirectNet’. Network ID: This field has no effect. Station No.: 0 When the device number exceeds two, a different station number is assigned to distinguish between the devices. 16Bit Data Swap: This field has no effect. 32Bit Data Swap: This field has no effect. Using Checksum: This field has no effect. Comm. Error Message Pop Up: When this item is checked, Xpanel displays a communication error message box for every Rx and Tx error. Otherwise (unchecked), Xpanel does not display a message for communication errors. This message box will close automatically after a few seconds. See the Communication Configuration section for more information about the remaining parameters. |
Parameter Setup: Cnet Frame Editor
...
Use device memories as shown in the table below.
Direct Variable | Data type | Remark |
%QX0.0.0 - %QX63.7.63 | BIT | Output image area |
%IX0.0.0 - %QX63.7.63 | BIT | Input image area |
%MX0 - %MX524287 | BIT | Direct variable area |
%MW0.0 - %MW32767.15 | BIT | Direct variable area |
%MD0.0 - %MD16383.31 | BIT | Direct variable area |
%QW0.0.0 - %QW63.7.3 | WORD | Output image area |
%IW0.0.0 - %QW63.7.3 | WORD | Input image area |
%MW0 - %MX32767 | WORD | Direct variable area |
%QD0.0.0 - %QD63.7.1 | DWORD | Output image area |
%ID0.0.0 - %QD63.7.1 | DWORD | Input image area |
%MD0 - %MD16383 | DWORD | Direct variable area |
Error Codes
When Xpanel communicates with a PLC it can receive a NAK that includes an error code.
For reference, see the error codes in the table below.
Error Code | Error type | Error factors and contents |
0001 | PLC System Error | Interface failure with PLC. |
0011 | Data Error | Possible causes:
|
1132 | Device Memory Error | Invalid characters were input. |
1232 | Data Magnitude Error | Read/Write request was over 60 Words. |
1332 | Data Type Inconformity | For each Read/Write attempt, if the data type of different blocks is mismatched, this error will occur. |
1432 | Data Value Error | Unable to transform data value to Hexadecimal. |
7132 | Invalid Variable Range Error | The requested address was outside of the PLC memory range. |
...