For normal communication, the following parameters must be set on the inverter side as noted.

  • CR/LF instruction presence/absence (Pr. 124): Mode 2 (with CR/LF)

  • Comm. response waiting time (Pr. 123): 9999 (use the waiting time data)

...

Inverter Setting Example

Parameter Number

Set Value

Description

1171

0

Station number 0 (any number between 0 to 31)

1181

192

19200 bps

1191

0

8 data bits, 1 stop bit

1201

0

No parity

121

9999

Do not use the communication retry

122

9999

Do not use the communication timeout

1232

9999

Response delay is dependent on the received frame.

1242

2

Use CR/LF terminator

(Note 1) Those parameters (117 to 120) must be matched with the settings of the Xpanel.

(Note 2) The parameters of 123 and 124 must be set as the value shown in this example. If those parameters are set as other values, Xpanel cannot communicate with the inverter.

Address Notation

The address of the tag in Xpanel has the following format:

Tag Type

Format

Example

Analog

[Symbol][Decimal Number]

P023

Digital

[Symbol][Decimal Number][.][Hexadecimal Number]

B022.F

Symbol

Address

Description

Inst. (R)

Inst. (W)

Access

P

000 - 999

Parameter Area

H00 – H63

H80 – HE3

R/W

D

008

Second Parameter

H6C

HEC

R/W

009

RAM Set Frequency

H6D

HED

010

EEPROM Set Frequency

H6E

HEE

023

Operation Mode

H7B

HFB

027

Link Parameter

H7F

HFF

B

011

Output Frequency (Speed)

H6F

 

R

012

Output Current

H70

 

013

Output Voltage

H71

 

016

Recent Alarm

H74

 

017

H75

 

018

H76

 

019

H77

 

022

Inverter Status (Bit mapped)

H7A

 

C

016

Alarm Definition Batch Clear

 

HF4

W

022

Run Command (Bit mapped)

 

HFA

024

All Parameter Clear

 

HFC

025

Inverter Reset

 

HFD

...