Logging Model Name

Enter the name of the Data Logging model. You may use alphanumeric characters, Korean alphabets, and special characters as the model name. You cannot use a duplicated model name.

Type

Periodic

Assign an interval for creating a new data block. The block will be created according to the assigned period, starting from 00:00 daily.

The actual data will be logged to the block after the delay time.

E.g.) When the start time is set to 4 minutes and the delay is 2 minutes, the block will be created every 4 minutes and the data will be stored 2 minutes after the new block is created.

Called

Select this option to create a new block by using the command expression “DataLog()”.

Trigger ON

Creates a new block when the assigned tag or address value turns ON. The data will be logged even if the status becomes OFF.

Trigger OFF

Creates a new block when the assigned tag or address value turns OFF. The data will be logged even if the status becomes ON.

Trigger Change

Creates a new block when the assigned tag or address value becomes OFF to ON or ON to OFF.

Enable Tag

Controls the block creation according to the assigned tag’s ON/OFF state. The block will be created when the tag is ON. The block will not be created when the tag is OFF.

On Time
(Once a Day)

Creates a block once a day at the assigned time. If the block is full, the data will no longer be logged to the block. When you select this option, any other method to create a block (such as Xpanel Reset) will not operate.

Start Time

Periodic

On Time

Creates a block according to the time.

Periodic: Assign the creation interval and the delay.

On Time: Assign the time of the day to create the block.

You can assign the time from 00:00 to 23:59.

In case of the a delay, you can assign a value up to 1439.

Trigger Tag On/Off/Change

Enable Tag

Creates the block when the assigned address or tag’s value changes from 0 to another value. You can assign the device address or tag by pressing the (blue star) button. In the case of the address, you can assign the data type (Bit/Word).

...

Item

Description

Type

Periodic

The data is logged according to the assigned interval. You can assign the interval from 1 to 30,000 seconds. (500min). This option operates when the block is created.

Tag Value

Logs the data when the assigned address or tag value changes from 0 to another value. You can assign the device address or tag by pressing the (blue star) button. In the case of the address, you can assign the data type (Bit/Word).

Log to CSV (Periodic/Tag Value, Daily)

Logs data according to the interval or the tag value. When you select this option, a CSV file will be created once a day, with the file name ‘YearMonthDay.csv'.

The log data of a single data logging model will be saved in the same CSV file.

Log to CSV (Periodic/Tag Value, Monthly)

Logs data according to the interval or the tag value. When you select this option, a CSV file will be created once a month, with the file name ‘YearMonth.csv'.

The log data of a single data logging model will be saved in the same CSV file.

Log to CSV (Periodic/Tag Value, New CSV on Startup)

When the starting condition is satisfied, the data logging model is activated and creates a new CSV file.

If using the main memory, the file will be stored in the ‘\Xpanel\CSV\Datalogging model name\YYYYMMDD_hhmmss.CSV’ path. After the model starts data logging, a new CSV file is created. You may store up to 3 files in the main memory. The older files will be removed automatically.

If using USB/SD memory, there is no absolute limit on the number of CSV files that can be stored. When there is not enough storage space, logged data cannot be updated as a CSV file.

※ This option is supported in XpanelDesigner 2.53 and above versions.

Standard

Period

Stores the data to the block according to the assigned interval. You can assign from 1 to 30000 seconds.

Addr/Tag

Logs the data when the assigned address or tag value changes from 0 to another value. You can assign the device address or tag by pressing the (blue star) button. In the case of the address, you can assign the data type (Bit/Word).

CSV save path

You can select the save path for the CSV file. If you wish to select USB or SD memory, the corresponding storage media must be connected to Xpanel. Logged data is not updated to the CSV file when there is not enough disk space.
Each save ‘Save’ path of the storage media is as follows:

※ This option is supported in XpanelDesigner 2.53 and above versions.

Main memory

Xpanel: XPANEL\CSV\Datalogging model name\

PC Runtime: Xpanel path\PCRun\CSV\Datalogging model name\

USB

USB memory\CSV\Datalogging model name\

SD

SD memory\CSV\Datalogging model name\

...

(blue star)

- Since the data is logged in the block unit, the block must be created in advance.

- If a block is full, you must create a new block to continue the data logging.

- If the number of blocks reached the maximum, the next block will be created after the deletion of the oldest block.

- Before saving the CSV file, check the volume of the storage. It is recommended to save the files in USB or SD memory.

- If the configuration of the data logging model has changed and the project is written to the Xpanel, the former project’s entire blocks will be deleted. (CSV files are not deleted.) Thus, back-up is needed if necessary.

- The data log file is stored in the Xpanel in the following location:

\ Xpanel\Log\“LogModelName”

...