For normal communication, the following parameters must be set on the inverter side as noted.

  • CR/LF instruction presence/absence (Pr. 124): Mode 2 (with CR/LF)

  • Comm. response waiting time (Pr. 123): 9999 (use the waiting time data)

...

Inverter Setting Example

Parameter Number

Set Value

Description

1171

0

Station number 0 (any number between 0 to 31)

1181

192

19200 bps

1191

0

8 data bits, 1 stop bit

1201

0

No parity

121

9999

Do not use the communication retry

122

9999

Do not use the communication timeout

1232

9999

Response delay is dependent on the received frame.

1242

2

Use CR/LF terminator

(Note 1) Those parameters (117 to 120) must be matched with the settings of the Xpanel.

(Note 2) The parameters of 123 and 124 must be set as the value shown in this example. If those parameters are set as other values, Xpanel cannot communicate with the inverter.

Address Notation

The address of the tag in Xpanel has the following format:

...

The addresses above can be used in both analog and digital tags. For more information on each point, please refer to the manual of the inverter.

Communication Cable Wiring

...