Create a new device | To create a new device, select ‘Tools’ → ‘I/O Devices’ or click the I/O Device Name: Assign a device name. This name will be used in the tag configuration window of the Database, accompanied by the ‘Station Name’. |
Select a device type | After selecting the ‘OK’ button in the previous step, the ‘Serial Communication Configuration’ dialog box will appear as shown in following picture: In this window, set the device type to ‘CIMON-PLC Loader’ and configure the remaining serial communication parameters. Ensure that these parameters are matched with the PLC configuration.
|
Create a station | Move to the ‘Station’ tab of the ‘Serial Communication Configuration’ dialog box. In this dialog box, all connected PLC stations can be configured and registered to the Xpanel. Press 'Add Station' to add a new station for each PLC. Each field can be configured with the following rules. Station Name: Give a name to the PLC. This name will be used in the database window accompanied by the ‘Device Name’. Station Type: Choose the type of connected PLC.
Network ID: N/A Station No: Specify a decimal number between 0 and 31. This number is only used by the CPU’s optional port or the SCnnA/B module. The station number is ignored by the standard loader port. 16bits Data Swap: N/A 32bits Data Swap: N/A Using Checksum: N/A Comm. Error Message Pop Up: If When this item is checked, Xpanel displays a communication error notification message box for every Rx and Tx error. Otherwise (unchecked), Xpanel does not display the a message for communication errors. Only when there is a data transmit error (writing a tag value to the station) will the notification message pop up. The This message box will close automatically after 5 a few seconds. |
Communication Setup: CIMON PLC
...
Wiring Diagram
RS-232C
All CPU models | |
CM1-SC01A,SC02A CM2-BPnnMxx-T |
...