Wiring
Make sure to check if the device’s power and external power supply is turned off before wiring, via a breaker, or similar unit. Failure to do so may cause electric shock or damage to the device.
Check the rated voltage of the product.
In case of terninal block connector type, make sure that power cord is connected properly.
Wiring Connecting the Xpanel Power Cord
If the power supply voltage exceeds the GP’s specified range, connect a voltage transformer.
Between the line and the ground, be sure to use a low noise power supply. If there is still an excessive amount of noise, connect a noise reducing transformer.
The power supply cord should not be bundled with or kept close to main circuit lines (high voltage, high current), or input/output signal lines.
Connect a surge absorber to handle power surges.
To reduce noise, make the power cord as short as possible.
When inputting power to the product, be sure to check the polarity (+, -) marked on the product before connecting. Incorrect polarity may cause product failure or fire.
● To avoid a short caused by loose ring terminals be sure to use ring terminals with an insulating sleeve. ● When the FG terminal is connected, be sure the wire is grounded. Not grounding the Xpanel unit will result in excess noise and vibration. ● The torque required to tighten these screws is 0.678_0.813 lbf*ft (0.5–0.6 N•m) ● Wire Range : AWG 14 - 26 SOL/STR, Wire Type : Cu |
---|