Connector

Pin No.

Name

Description

image-20240912-044825.png

1

RDB

Receive Data B

2

RDA

Receive Data A

3

GND

Ground

4

SDB

Send Data B

5

SDA

Send Data A

...

COM2: RS-

...

232C

This interface is used for the connection between Xpanel and target device via an RS-232C cable.

Connector

Pin No.

Name

DescriptionPort

image-20240912-045150.png

1

SDA

Send Data A

COM1

 -

2

RD

Receive DataCOM2

3

TD

Transmit Data

COM2

4

RDA

Receive Data A

COM1 -

5

SG

Signal GroundCOM1, COM2

6

SDB

Send Data B

COM1

 -

 -

7

RTS

Request To Send

COM2

8

CTS

Clear To SendCOM2

9

RDB

Receive Data B

COM1 -

 -

● Normal communication is not guaranteed when using USB connector as a communication port in ordinary times.

● In case of RS-485 cable (2wire) connection, connect only both SDA and SDB lines.

● The RS-485 of the Xpanel runs under auto toggle mode.