Versions Compared
Version | Old Version 7 | New Version 8 |
---|---|---|
Changes made by | ||
Saved on |
Key
- This line was added.
- This line was removed.
- Formatting was changed.
Anchor | ||||
---|---|---|---|---|
|
Table of Contents | ||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
|
Tag Editor
Item | Description |
![]() Add Tag | Adds a tag. |
![]() Add Tag Group | Adds a tag group. |
![]() Edit Tag | Edits the selected tag |
![]() Copy Tag | Saves the selected tag’s content in the clipboard. |
![]() Paste Tag | Pastes the tag’s content in a Tag Editor pane, Spreadsheet, or Notepad. |
![]() Delete Tag | Deletes the selected tag. |
![]() Tag Count | Opens a pop-up window that displays the number of created tags for each type or device. |
![]() Expand All | Shows all dropdown content within the Tag Editor pane. |
![]() Collapse All | Hides all dropdown content within the Tag Editor pane. |
Data Types
Data Type | Description | Range |
BOOL | Represent ON/OFF status, 0 or 1, True or False, or other values with only two possible states. If a boolean tag is tied to a device address with more than one bit, then any value other than one will be treated as a one. | 0 – 1 |
REAL(FLOAT) | 32-bit floating-point number. Enables the Clamp Mode, Deadband Type, and Scale Mode advanced options. | -3.403e+038 – 3.403e+038 |
LREAL(DOUBLE) | 64-bit floating-point number. Enables the Clamp Mode, Deadband Type, and Scale Mode advanced options. | -1.798e+308 – 1.798e+308 |
SINT(INT8) | Signed 8-bit integer. Enables the Encoding, Clamp Mode, Deadband Type, and Scale Mode advanced options. | -128 – 127 |
INT(INT16) | Signed 16-bit integer. Enables the Encoding, Clamp Mode, Deadband Type, and Scale Mode advanced options. | -32768 – 32767 |
DINT(INT32) | Signed 32-bit integer. Enables the Encoding, Clamp Mode, Deadband Type, and Scale Mode advanced options. | -2147483648 – 2147483647 |
LINT(INT64) | Signed 64-bit integer. Enables the Clamp Mode, Deadband Type, and Scale Mode advanced options. | -9223372036854775808 – 9223372036854775807 |
USINT(UINT8) | Unsigned (non-negative) 8-bit integer. Enables the Encoding, Clamp Mode, Deadband Type, and Scale Mode advanced options. | 0 – 255 |
UINT(UINT16) | Unsigned (non-negative) 16-bit integer. Enables the Encoding, Clamp Mode, Deadband Type, and Scale Mode advanced options. | 0 – 65535 |
UDINT(UINT32) | Unsigned (non-negative) 32-bit integer. Enables the Encoding, Clamp Mode, Deadband Type, and Scale Mode advanced options. | 0 – 4294967295 |
ULINT(UINT64) | Unsigned (non-negative) 64-bit integer. Enables the Clamp Mode, Deadband Type, and Scale Mode advanced options. | 0 – 18446744073709551615 |
STRING | Stores a string value composed of ASCII characters. For local tags, strings up to 22 characters long can be created. For remote tags, strings will use a contiguous data block on the target device. |
Tags
Tag Type | Description |
---|---|
Remote Tag | Write and read their value to and from external devices. When the value of a remote tag changes, it is immediately written to the associated device (via the chosen connection method - some methods may be faster than others). |
Virtual Tag | Allow access to the Xpanel’s gateway, allowing various features (i.e., alarming, data logging, etc.). Other devices can also access shared tags over a common protocol while utilizing the Data Server feature. |
Virtual (Runtime Only) Tag | Used internally within Xpanel. They simulate devices and processes, process input data, and store data describing the application state. Each tag has a specific sub-type: BOOL, REAL, LREAL, SINT, INT, DINT, LINT, USINT, UINT, UDINT, ULINT, or STRING. |
Edit Tag
General
This setting contains pertinent data for all tag types.
Item | Description |
Tag Name | Assigns a name to the user’s tag. |
Path | Displays the group path of the tag. |
Data Type | Allows the user to select from 12 possible data types. The available fields in the advanced options tab will change based on the selected data type. |
I/O Device | For remote tags, select the external device to associate the tag with. The user can check the name of external devices by clicking Tools > I/O Device Editor. The user can also select Virtual or Virtual (Runtime Only) for those respective tag types. |
I/O Address | For remote tags, enter the external device address to associate the tag with. The user must enter the address using the device’s addressing method. For example, for a CIMON PLC, valid bit addresses include “X00”, “Y1E”, etc. For Virtual or Virtual (Runtime Only), enter the system tag values for specific functions. |
Bit Access | Enables or disables the use of Bit Number. This is not available for data types BOOL, REAL, LREAL, or STRING. |
Bit Number | Assigns the value of the bit number to target in the given I/O Address. |
Initial Value | Assigns the value of the tag to be set on project startup. |
Persistent | When this option is true, the last state of the tag is stored when the project is closed. When the user executes the project again, the tag values will be reloaded. |
Value Changed | With this option enabled, a user-defined script or action list will be performed when the tag value changes. |
Quality Changed | With this option enabled, a user-defined script or action list will be performed when the quality of the tag changes. In this case, quality refers to the communications status of the tag. |
Advanced
Item | Description | |
Encoding | Selecting the BCD option from the drop down menu enables binary-coded decimal encoding. With this mode enabled, a binary sequence will represent the analog tag’s value. Note that binary-coded decimal does not function the same as converting a decimal number to binary. This option is only available for data types SINT (INT8), INT (INT16), DINT (INT32), USINT(UINT8), UINT (UINT16), UDINT (UINT32). | |
Clamp Mode | This option dictates how the tag will handle values outside of the specified maximum/minimum values. Note that this setting only applies to write requests, and will not change values read from the PLC. | |
Clamp High | To use this feature, select Clamp High from the drop-down menu. Next, enter the desired Engineering Max value. Any tag value greater than the assigned Engineering Max value will be overwritten to the Engineering Max value. | |
Clamp Low | To use this feature, select Clamp Low from the drop-down menu. Next, enter the desired Engineering Min value. Any tag value less than the assigned Engineering Min value will be overwritten to the Engineering Min value. | |
Clamp Both | To use this feature, select Clamp Both from the drop-down menu. Next, enter the desired Engineering Max and Engineering Min values. Any tag value greater than the assigned Engineering Max value will be overwritten to the Engineering Max value, and any tag value less than the assigned Engineering Min value will be overwritten to the Engineer Min value. | |
Reject High | To use this feature, select Reject High from the drop-down menu. Next, enter the desired Engineering Max value. Any tag value greater than the assigned Engineering Max value will be discarded, and the tag value will remain at the last recorded tag value. | |
Reject Low | To use this feature, select Reject Low from the drop-down menu. Next, enter the desired Engineering Min value. Any tag value less than the assigned Engineering Min value will be discarded, and the tag value will remain at the last recorded tag value. | |
Reject Both | To use this feature, select Reject Both from the drop-down menu. Next, enter the desired Engineering Max and Engineering Min values. Any tag value greater than the assigned Engineering Max value will be discarded, and the tag value will remain at the last recorded tag value. Any tag value less than the assigned Engineering Min value will be discarded, and the tag value will remain at the last recorded tag value. | |
Deadband Type | Filters the original input data and discards any new input data that falls within a specified range of the last recorded tag value. | |
Absolute | To use this feature, select Absolute from the Deadband drop down menu. Next, assign any numeric value in the Deadband field. If the absolute difference between the current tag value and the last recorded tag value is greater than the Deadband value, the current value of the tag is sent. If the absolute difference is less than the Deadband value, the current value is filtered. Example: Select a DINT tag type and an Absolute Deadband type. For a Deadband of 10: Last Recorded Tag Value: 40 Current Tag Value: 12 Absolute Difference = |Last Recorded Tag Value - Current Tag Value| For this case, the absolute difference between the two tags is 28. The absolute difference is higher than the Deadband, so the current tag value will be recorded. Next, say that the last recorded tag value remains at 40 with a new current tag value of 32. The absolute difference in this case would be less than the deadband, so the current tag value would be filtered and the tag value would remain as the last recorded tag value. | |
Percent | To use this feature, select Percent from the Deadband drop-down menu. Next, assign a numeric value between 1 and 100 in the Deadband field. If the percent difference between the current tag value and the last recorded tag value is greater than the Deadband value, the tag's current value is sent. The current value is filtered if the percent difference is less than the Deadband value. Example: Select a DINT tag type and a Percent Deadband type. For a Deadband of 10: Last Recorded Tag Value: 40 Current Tag Value: 12 Percent Difference = |Last Recorded Tag Value - Current Tag Value| /(Last Recorded Tag Value) * 100 For this case, the percent difference between the two tags is 70%. The percent difference is higher than the Deadband, so the current tag value will be recorded. Next, say that the last recorded tag value remains at 40 with a new current tag value of 37. The percent difference in this case would be less than the deadband, so the current tag value would be filtered and the tag value would remain as the last recorded tag value. | |
Scale Mode | Converts the original input data into a new value using one of four methods. | |
Linear Range | To use this feature, select Linear Range from the drop-down menu. Next, enter the desired Raw Low, Raw High, Scaled Low, and Scaled High values. With this option, the tag value will be linearly scaled such that the Raw Low is converted to the Scaled Low and the Raw High is converted to the Scaled High. Intermediate values are scaled linearly. For a given input (raw) value, the exact output (tag) value can be calculated using the formula below: Tag Value = (Input Value – Raw Low) / (Raw High – Raw Low) * (Scaled High– Scaled Low) + Scaled Low Example: Select a REAL tag type. Set the Raw Low to zero and the Raw High to one. Set the Scaled Low to zero and the Scaled High to 100. Now, PLC values (on the left) will be converted to the following tag values (on the right): -17.0 becomes 0 Any input value below the Raw Low will be converted to the Scaled Low. Any input above the Raw High will be converted to the Scaled High. For a given tag value, the corresponding input value can be calculated using the formula below: Input Value = (Tag Value – Raw Low) / (Scaled High – Scaled Low) * ( Raw High– Raw Low) + Raw Low | |
Linear Slope | To use this feature, select Linear Slope from the drop-down menu. Next, enter the desired Slope and Intercept values in their respective fields. With this option, the tag value will be calculated using the formula below: Tag Value = (Input Value * Slope) + Intercept Example: Select an analog tag with data type UINT. For a Slope of 0.1 and an Intercept of 10: Minimum value: (0 * 0.1) + 10 = 10, For a given tag value, the corresponding input value can be calculated using the formula below: Input Value = (Tag Value – Intercept) / Slope | |
Square Root | To use this feature, select Square Root from the drop-down menu. Next, enter the desired Raw Low, Raw High, Scaled Low, and Scaled High values. With this option, the tag value will be exponentially scaled, such that the Raw Low is converted to the Scaled Low and the Raw High is converted to the Scaled High. Intermediate values are scaled exponentially, with a fixed exponent of 1/2. For a given input (raw) value, the exact output (tag) value can be calculated using the formula below: Tag Value = (Scaled High – Scaled Low) * sqrt((Input Value - Raw Low) /(Raw High – Raw Low)) + Scaled Low Any input value below the Raw Low will be converted to the Scaled Low. Any input above the Raw High will be converted to the Scaled High. For a given tag value, the corresponding input value can be calculated using the formula below: Input Value = ((Tag Value – Scaled Low) / (Scaled High – Scaled Low))^2 * ( Raw High – Raw Low) + Raw Low | |
Polynomial | To use this feature, select Polynomial from the drop-down menu. Next, enter the desired Exponent, Slope, and Intercept values. With this option, the tag value will be exponentially scaled. For this option, the tag value will be calculated using the formula below: Tag Value = Slope * (Input Value)^Exponent + Intercept For a given tag value, the corresponding input value can be calculated using the formula below: Input Value = ((Tag Value - Intercept)/(Slope)) ^ (1/Exponent) |
Advanced - STRING
The following options are only available for the data type STRING.
Item | Description |
Use Device Encoding | |
String Encoding | |
Use Device Encoding Method | |
String Encoding Method | |
Max Length | Assign the maximum string length that can be written to the tag. For local tags, the user can choose a value between 1 and 2147483647. For remote tags, the maximum length is only limited by the device memory. Note: Be careful to avoid overlapping device addresses. For example, if one string tag “STR1” begins at address D00 on a CIMON PLC, and another string tag begins at address D07, then STR1 should be no longer than 14 characters (7 words * (16 bits/word) / (8 bits/character) = 14 characters). Otherwise, editing one string may affect the other. |
I/O Address Editor
Virtual
Type | Value | Description |
Normal | N/A | |
System | CPU Architecture | |
Operating System | ||
OS Kernal Type | ||
OS Kernal Version | ||
Device Host Name | ||
System Username | ||
Datetime String | ||
Unix Timestamp | ||
System Uptime (ms) | ||
Current Language | ||
Data Log | Enable Status | |
I/O Device | Connection Status |
Virtual (Runtime Only)
Type | Value | Description |
Normal | N/A | |
System | CPU Architecture | |
Operating System | ||
OS Kernal Type | ||
OS Kernal Version | ||
Device Host Name | ||
System Username | ||
Datetime String | ||
Unix Timestamp | ||
System Uptime (ms) | ||
Current Language | ||
Screen | Width (Pixels) | |
Height (Pixels) | ||
Resolution (WxH) | ||
Page | Current Page Name | |
Current Page Number | ||
Security | Current Username | |
Data Log | Enable Status | |
I/O Device | Connection Status |