This driver allows for communication with CIMON devices (PLCs, XPanels, IPCs) using a standard Ethernet connection.
Communication Settings: Xpanel
I/O Device Configuration | To create a new device, click Tools > I/O Device Editor… > click the + icon > click Ethernet for Connection Type > select CIMON PLC (HMI Protocol) for Device Type. |
I/O Device Settings
| Once the connection type, device name, and device type have been assigned, the I/O Device Editor window populates with the default settings for the selected communication protocol. After selecting the correct Connection Type and Device Type, match the remaining settings to the target I/O device’s communication settings. |
See the Ethernet Communication Configuration section for more information.
Communication Settings: PLC
Communication Module | If using one of the following PLC modules to communicate with Xpanel, the card settings must be configured in CICON:
All communication parameters must match the settings chosen during the I/O device configuration in Canvas. Once the correct parameters have been entered, click Write while online with the PLC to update the communication parameters. |
CPU Built-in Communication Port | If using a built-in CPU (PLC) ethernet port to communicate with Xpanel, the channel settings must be configured in CICON as shown below: This connection option is available with the following models:
|
Address and Supported Devices
The memory areas listed below are provided for general purposes. The actual available memory area and range of each area should be checked with the manual for the connecting device.
...
Area | Device | Bit Range | Word Range | Access |
---|---|---|---|---|
Input | X | X0000 - X511F | X0000 - X5110 | R/W |
Output | Y | Y0000 - Y511F | Y0000 - Y5110 | R/W |
Binary | M | M0000 - M999F | M0000 - M9990 | R/W |
Binary | L | L0000 - L999F | L0000 - L9990 | R/W |
Non-Volatile Binary | K | K0000 - K999F | K0000 - K9990 | R/W |
Status | F | F0000 - F127F | F0000 - F1270 | R |
Timer | T | T0000 - T4095 | - | R/W |
Counter | C | C0000 - C4095 | - | R/W |
Control | S | S00 - S99 | - | |
Integer | D | - | D00000 - D31999 | R/W |
Index | R | - | - | - |
Timer - Current Count | TC | - | TC0000 - TC4099 | R/W |
Timer - Timer Set | TS | - | TS0000 - TS4099 | R/W |
Counter - Current Count | CC | - | CC0000 - CC4099 | R/W |
Counter - Count Set | CS | - | CS0000 - CS4099 | R/W |
Integer | Z | - | Z0000 - Z1023 |
Supported Tag Type
Data Type
Canvas Type
Supported
Binary-coded decimal (BCD)
Boolean
BOOL
✔️
-
UInt8
USINT
✔️
✔️
UInt16
UINT
✔️
✔️
UInt32
UDINT
✔️
✔️
UInt64
ULINT
❌
❌
Int8
SINT
✔️
✔️
Int16
INT
✔️
✔️
Int32
DINT
✔️
✔️
Int64
LINT
❌
❌
Float32
REAL
✔️
-
Float64/Double
LREAL
❌
-
String
STRING
✔️
Communication Cable Wiring
This interface is satisfied with standard IEEE802.3 about the 10BaseT/100BaseTX. You can configure the cable and allocation pin number of RJ45 as shown below.
...