This driver uses a standard Ethernet connection to communicate with EtherNet/IP devices.
Communication Settings: Xpanel
I/O Device Configuration | To create a new device, click Tools > I/O Device Editor… > click the + icon > click Ethernet for Connection Type > select Allen-Bradley EtherNet/IP for Device Type. |
I/O Device Settings
| Once the connection type, device name, and device type have been assigned, the I/O Device Editor window populates with the default settings for the selected communication protocol. After selecting the correct Connection Type and Device Type, match the remaining settings to the target I/O device’s communication settings. |
See the Ethernet Communication Configuration section for more information.
Communication Settings: PLC
ControlLogix/CompactLogix |
The next steps are for PCCC communication. If you would like to use tag-based addressing, please skip the next three steps and resume with setting an IP address.
All communication parameters must match the settings chosen during the I/O device configuration in Canvas. Once the correct parameters have been entered, click Write while online with the PLC to update the communication parameters. |
MicroLogix |
|
Micro800 |
Address and Function Codes
The memory areas listed below are provided for general purposes. The actual available memory area and range of each area should be checked with the manual for the connecting device.
...
Symbol | Bit Range | Word Range | Name |
---|---|---|---|
O | O:0.0/0 – O:30.255/15 | O:0.0 – O:30.255 | Output |
I | I:0.0/0 – I:30.255/15 | I:0.0 – I:30.255 | Input |
S | S:0/0 – S:163/15 | S:0 – S:163 | Status |
B | B3:0/0 – B3:255/15 B9:0/0 – B255:255/15 | B3:0/0 – B3:255/15 B9:0/0 – B255:255/15 | Binary |
N | N7:0/0 – N7:255/15 N9:0/0 – N255:255/15 | N7:0 – N7:255 N9:0 – N255:255 | Integer |
F |
| F8:0 – F255:255
| Float |
L |
| L9:0 – L255:255
| Long |
ST |
| ST9:0 – ST255:255 | String |
T | T4:0.0/0 – T4:255.2/15 T9:0.0/0 – T255:255.2/15
Txx:nn.0/15 = Enable(EN) Txx:nn.0/14 = Timer Timing(TT) Txx:nn.0/13 = Done(DN) | T4:0.0 – T4:255.2 T9:0.0 – T255:255.2
Txx:nn.1 = Preset Value(PRE) Txx:nn.2 = Accumulated Value(ACC) | Timer |
C | C5:0.0/0 – C5:255.2/15 C9:0.0/0 – C255:255.2/15
Cxx:nn.0/15 = Count up enable(CU) Cxx:nn.0/14 = Count down enable(CD) Cxx:nn.0/13 = Done(DN) Cxx:nn.0/12 = Overflow(OV) Cxx:nn.0/11 = Underflowt(UN) Cxx:nn.0/10 = Update Accumulator(UA) | C5:0.0 – C5:255.2 C9:0.0 – C255:255.2
Cxx:nn.1 = Preset (PRE) Cxx:nn.2 = Accumulated Value(ACC) | Counter |
R | R6:0.0/0 – C6:255.2/15 R9:0.0/0 – R255:255.2/15
Rxx:nn.0/15 = Enable(EN) Rxx:nn.0/14 =Update Enable(EU) Rxx:nn.0/13 = Done(DN) Rxx:nn.0/12 = Stack Empty(EM) Rxx:nn.0/11 = Error(ER) Rxx:nn.0/10 = Upload(UL) Rxx:nn.0/9 = Inhibit(IN) Rxx:nn.0/8 = Found(FD) | R6:0.0 – R6:255.2 R9:0.0 – R255:255.2
Rxx:nn.1 = Length value Rxx:nn.2 = position value | Control |
Communication Cable Wiring
This interface is satisfied with standard IEEE802.3 about the 10BaseT/100BaseTX. You can configure the cable and allocation pin number of RJ45 as shown below.
...