Versions Compared

Key

  • This line was added.
  • This line was removed.
  • Formatting was changed.

Item

Specification

Processing System

Multi-task (high speed, multiprocessing)

(*) Memory Capacity

4 GB (2 GB for logging data)

Function Setting

Using CICON software (PLC loader program)

App Upgrade Feature

Application downgrade/upgrade feature is supported

CM1-CPU

Connection Method

Connection with RS-232C port or USB at CPU module
Passthru connection through communication module (EC Series)

Configuration

Network setting, logging type, logging cycle, data list, Log file ID (*)

Monitoring

The number of clients, communication status, logged data transmission status, progress of data logging, CPU status, memory consumption (%), memory overflow (automatic dump, deletion) status, error information

Communication Function

Communication Standard

Ethernet 10/100 Mbps or 1 Gbps

Protocol

TCP, CIMON HMI Ethernet Protocol

Access limitation

Simultaneous connections of up to 5 clients (Up to 3 clients can simultaneously access when using FTP feature)

Comm. Cable

Over CAT.5 STP (Shielded Twisted pair) cable

Maximum Distance

Maximum 100 m for preliminary physical connection with the network device (host system, hub, router, etc.)

Logging Function

Logging Type

Event Sampling, trigger monitoring (*)

Range of Cycle

1 – 327,67 (x L ms)

L (*) = Time interval scale (1, 10, 100)

The value is fixed at L = 10 below V2.0

Range of Deadband

0 ~ 65535(*)

The value is fixed at ‘0’ in under V2.0.

Logging

Device Type

X, Y, M, L, K, F, T, TC, TS, C, CC, CS, S, D, Z, R Device in PLC CPU

Data Type

Bit, Byte, Word, DWord, DDWord

Data Storage

Non-volatile memory (ROM) storage (Does not require a battery)

Data Capacity

24 bytes for saving in a single device type

Data Managing

Storage Method

Event sampling: Saving data by date/hour

Trigger monitoring (*): Saving data by file ID (Including time information)

Delete Method

Automatic delete: The oldest data is deleted when memory is at capacity (Overflown)

Manual delete: All logged data, (*) event sampling log data, (*) trigger monitoring log data

Compatible Host System

SCADA V3.90 and above version including ‘Historian’ feature

Recommended system requirements: 64-bit version of Windows, 8GB RAM

Range of Time Synchronization Frequency

1–32767 (x10 sec)

Error Display

LED, Display error code (LG02G configuration/monitoring window in CICON)

Comm. Status Display

LED, Display error code (LG02G configuration/monitoring window in CICON)

Number of Input/Output Points

16 points (input 16 points/output 16 points)

Current Consumption

136 mA

Weight

113.5 g