Create a new device | To create a new device, select [Tools] → [I/O Devices] or click the The following picture shows the first step in creating a new device: I/O Device Name: Give a device name. This name will be used in the tag database, accompanied by the ‘Station Name’. |
Select a device type | After selecting the [Ok] button in the previous step, the ‘Serial Communication Configuration’ dialog box will appear as shown in the following picture: In this window, set the ‘Device Type’ to ‘SIEMENS S7 MPI’ and configure the remaining communication parameters. These parameters must match those chosen for the PLC. Local ID: Give a station (node) number for the Xpanel. This number must not be used by any of the S7 MPI PLCs. The node number can be an integer value between 0 and 126. Network Opt: Designate the maximum station (node) number used in the connected network. If the Xpanel is the unique master in the network, the integer value of (1,000+maximum station number) should be designated. Ex) 15, 31, 63, 126 (when the Xpanel is not the unique master in the network). See the Communication Configuration section for more information about the remaining parameters. |
Create a station | Move to the [Station] tab of the ‘Serial Communication Configuration’ dialog box. In this dialog box, connected PLC stations can be configured and registered to the Xpanel. Each field can be configured with the following rules: Station Name: Give a name to the PLC. This name will be used in the tag database, accompanied by the ‘Device Name’. Station Type: Choose ‘S7 MPI’ (this is the only available option). Network ID: N/A Station No: Specify a decimal number between 0 and 126. This must be a unique number, matched with the settings of the chosen PLC. See the Communication Configuration section for more information about the remaining parameters. |
...