Communication Setup: Xpanel
...
The symbol character has to be placed in the first position of the address string. The address number follows the symbol character.
Area | Symbol | Analog Tag | Digital Tag | Read | Write |
Coil | 0 |
| 000001 - 029999 (1) | 1 | 5 |
Input | 1 |
| 100001 - 129999 | 2 |
|
Holding Register | 4 | 400001 - 429999 |
| 3 | 6, 16 (2) |
Input Register | 3 | 300001 - 329999 |
| 4 |
|
(1) The symbol character does not behave as a number. For example, 400100 and 4100 designate the same memory area (holding register 100).
(2) Code 16 is issued for writing double words or when the recipe write function is activated. When writing single words, code 6 is used.
...
This interface is satisfied with standard IEEE802.3 about the 10BaseT/100BaseTX. You can configure the cable and allocation pin number of RJ45 as shown below.
...
RJ45 Connector | RJ45 Jack |
Direct Cable: Host ↔︎ HUB
...
Cable | No | Color | Color | No | Cable |
1 | Orange/White | Orange/White | 1 | ||
2 | Orange | Orange | 2 | ||
3 | Green/White | Green/White | 3 | ||
4 | Blue | Blue | 4 | ||
5 | Blue/White | Blue/White | 5 | ||
6 | Green | Green | 6 | ||
7 | Brown/White | Brown/White | 7 | ||
8 | Brown | Brown | 8 |
Crossover Cable: Host ↔︎ Host
...
Cable | No | Color | Color | No | Cable |
1 | Orange/White | Green/White | 1 | ||
2 | Orange | Green | 2 | ||
3 | Green/White | Orange/White | 3 | ||
4 | Blue | Blue | 4 | ||
5 | Blue/White | Blue/White | 5 | ||
6 | Green | Orange | 6 | ||
7 | Brown/White | Brown/White | 7 | ||
8 | Brown | Brown | 8 |