For normal communication, the following parameters of the inverter have to be properly configured.

Function Code

Item

Value

Description

C070

Data command source

02

Digital operator

03

RS-485 connector

04

Expansion card #1

05

Expansion card #2

C071

 

Baud rate

02

Loopback test

03

2400 bps

04

4800 bps

05

9600 bps

06

19200 bps

C072

Node address

1 to 32

Node or station address

(unique to each inverter or device)

C073

Data bits

07

7 bits

08

8 bits

C074

Parity

00

None

01

Even parity

02

Odd parity

C075

Stop bits

01

1 bit

02

2 bits

C078

Wait time

0 to 1000

0 to 1000 ms

(time that the inverter waits to respond to the network master)

...