Tag Type | Format | Example |
Analog | [Symbol][Address] | DM0012 |
Digital | [Symbol][Address] | R0215 |
Note: address numbers are in decimal, not hexadecimal format.
...
Symbol | Description | Address Range | Type | Access |
CC | Counter: Current Value | 0-249 | Analog | R/W |
CP | Counter: Preset Value | 0-249 | Analog | R/W |
C | Counter Contact | 0-249 | Digital | R/W |
CTHC | High Speed Counter: Current Value | 0 - 1 | Analog | R/W |
CTHP | High Speed Counter: Preset Value | 0 - 1 | Analog | R |
CTH | High Speed Counter: Contact | 0 - 1 | Digital | R |
CTCC | High Speed Counter Comparator: Current Value | 0 - 3 | Analog | R |
CTCP | High Speed Counter Comparator: Preset Value | 0 - 3 | Analog | R/W |
CTC | High Speed Counter Comparator: Contact | 0 - 3 | Digital | R/W |
TC | Timer: Current Value | 0-249 | Analog | R/W |
TP | Timer: Preset Value | 0-249 | Analog | R/W |
T | Timer: Contact | 0-249 | Digital | R/W |
TM | Temporary Data Memory | 0 – 31 | Analog | R/W |
DM | Data Memory | 0 - 1999 | Analog | R/W |
R | Relay (I/O, Internal AUX, Special AUX) | 0-17915 | Digital | R/W |
AT | Digital Trimmer | 0 - 1 | Analog | R |
The Keyence KV mode protocol does not support block data read and write functions. Because of this, double word (INT32, UINT32, BCD32, UBCD32, FLOAT) data types are not supported. When using this protocol, be sure to check your usage of double words, especially when using the following functions of Xpanel: - Recipe - XY / SPC / Scope Trend. |
---|
...