Symbol | Memory | Analog Tag | Digital Tag | Format | Data | ||
10GM | 20GM | 10GM | 20GM | ||||
M | Aux Relay | - | - | M000-M511 | M000-M511 | Dec | Bit |
SM | Special Relay | - | - | SM0000-SM0175 | SM0000-SM0175 | Dec | Bit |
X | Input | - | - | X000-X003 X375-X377 | X000-X067 X372-X377 | Oct | Bit |
Y | Output | - | - | Y000-Y005 | Y000-Y067 | Oct | Bit |
D | Data Register | D000-D1999 | D000-D3999 | - | - | Dec | Word |
SD | Special data register | SD000-SD0313 | SD000-SD0599 | - | - | Dec | Word |
V | - | V000-V007 | V000-V007 | - | - | Dec | Word |
Z | - | Z000-Z007 | Z000-Z007 | - | - | Dec | Dword |
Note: SM addresses begin in the M register at the address M9000. Likewise, SD addresses begin in the D register at the address D9000. For example, the address SD0003 corresponds to PLC address D9003.
Communication Cable Wiring
...