Select [Tools] - [I/O Devices] or click the (blue star) icon from the Main Toolmain toolbar.

To create a device, see the image below.

...

I/O Device Name: Give a device name.

...

Station Name

Give a name to the PLC. This name will be used in the database window accompanied with by the ‘Device Name’.

Station Type

Choose the ‘MicroLogix’ (no other type).

Network ID

This field has no effect.

Socket Port No.

Default The default is set as 4481 for MicroLogix.

16Bit Data Swap

Data is obtained by switching between high and low byte in word swapping bytes of the word- or double-word-sized data.

32Bit Data Swap

Data is obtained by switching between high and low byte swapping words in double-word-sized data.

String Data Swap

 Data Data is obtained by switching between high and low byte in string bytes of string word data.

Comm. Error Message Pop Up

With this feature ON, the communication error message appears when Xpanel detects a “Send/Receive” error. The error message will disappear after 5 seconds.

Fast Mode

This field has no effect.

Fixed ATVXEL Socket Port

Enables the ATVXEL Socket Port No.

ATVXEL Socket Port No.

Choose a Socket Port No. for the Xpanel.

I/O Device Write Enable

Enables writing to the I/O device.

Data Request Size Limit

Enables the 'WORD' and ‘BIT’ boxes below. Input the maximum word and bit data desired.

...

  • Run RSLogix 500.

  • Select [Comms] → [Upload…] from the menu, and upload a project.

...

  • Double-click on ‘Channel Configuration’ [Channel Configuration] from the project window to open the ‘Channel Configuration’ window.

  • Go to the ‘Chan[Chan.1 - System’ System] tab in the ‘Channel Configuration’ window.

...

This is an interface for communication between the TOUCH/PPC and the Device by Ethernet. This complies with IEEE802.3 for 10 Base / 100 Base TX10Base/100BaseTX. Refer to the PIN number and cable for RJ45 as shown below.

...