Item | Description |
Buffer | Assign the number of data to be displayed on the object. Each pen’s data will be displayed according to the value assigned in this field. You may assign the value from 2 to 800. |
Sampling | Indicates the sampling method. If you select Periodic, the data will be updated according to the assigned sampling interval. If you select Trigger, the data will be updated when the assigned tag value changed from zero to a non-zero value. |
Sampling Interval | This field will be enabled when you select the Periodic option. The interval unit is 100ms and you may assign a value from 1 to 65535. |
Trigger Tag | This field will be enabled when you select the Trigger option. You may assign a tag or an address which will cause operation. Press the |
Screen Control Tag | Assign a tag to control the Log Trend. 0: Allows data logging and initiates trend operation. 1: Stops data logging and ceases trend operation. 2: Initializes the data logging and trend operation. The data logging and trend operation will be cease after the initialization. |
Data Point | Configures the size of the data point. You may assign the value from 0 to 1024. |
Using Multi-Channel | Select this option to individualize the graph pen by pen. The topmost graph displays the data of pen 1. |
Draw Border | Shows or hides the border of the graph. |