Configuring CIMON-SCADA

To properly use the Xpanel Data Server function, you must configure the associated SCADA project as well.

a)     In CimonD, select [Tools] – [I/O Device]. Press [New Device] to bring up the [I/O Device Selection] window as shown below. Select ‘CIMON-ATVXEL Ethernet’ and designate a name for the device.

...

b)     In the next window, press [Add Station] to enter the configuration of the Xpanel. Press [IP Addr.] to enter the target device’s IP address. You may also assign scan time, time out, etc.

...

Item

Description

Station Name

c)     Press [Add COM Block] button to assign a data block for the communication.

...

d)     Go to [COM Port] tab and enter the local PC’s address.

...

e)     Register a real tag according to the COM block’s data range.

...

f)     Execute CimonX to check the operation.