Cable | No. | Color | Color | No. | Cable |
1 | Orange/W | Orange/W | 1 | ||
2 | Orange | Orange | 2 | ||
3 | Green/W | Green/W | 3 | ||
4 | Blue | Blue | 4 | ||
5 | Blue/W | Blue/W | 5 | ||
6 | Green | Green | 6 | ||
7 | Brown/W | Brown/W | 7 | ||
8 | Brown | Brown | 8 |
Crossover Cable: Host ↔︎ Host
Cable | No. | Color | Color | No. | Cable |
1 | Orange/W | Green/W | 1 | ||
2 | Orange | Green | 2 | ||
3 | Green/W | Orange/W | 3 | ||
4 | Blue | Blue | 4 | ||
5 | Blue/W | Blue/W | 5 | ||
6 | Green | Orange | 6 | ||
7 | Brown/W | Brown/W | 7 | ||
8 | Brown | Brown | 8 |
Device Memory Range
Within XpanelDesigner, you may use the following device memory addresses to reference the connected PLC.
Direct Variable | Data type | Remark |
%QX0.0.0 - %QX63.7.63 | BIT | Output area |
%IX0.0.0 - %QX63.7.63 | BIT | Input area |
%MX0 - %MX524287 | BIT | Direct variable area |
%MW0.0 - %MW32767.15 | BIT | Direct variable area |
%MD0.0 - %MD16383.31 | BIT | Direct variable area |
%QW0.0.0 - %QW63.7.3 | WORD | Output image area |
%IW0.0.0 - %QW63.7.3 | WORD | Input image area |
%MW0 - %MX32767 | WORD | Direct variable area |
%QD0.0.0 - %QD63.7.1 | DWORD | Output area |
%ID0.0.0 - %QD63.7.1 | DWORD | Input area |
%MD0 - %MD16383 | DWORD | Direct variable area |
Note: “Direct“ variable areas support both read and write operations.
...